166
Q9 ASD Installation and Operation Manual
Ext. Comm. Cfg. 2
No Path — Direct Access Only
This parameter sets the Modbus RTU network characteristics: Baud Rate, Parity,
and Stop Bits. See the table below for the parameter settings.
Direct Access Number — F883
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255 (only 0 – 19 effective)
Ext. Comm. Cfg. 3
No Path — Direct Access Only
This parameter Enables/Disables the network time-out timer. The timer is enabled
by setting this parameter to a non-zero value (1 – 255). The timer is disabled by
setting this value to zero.
Once started, the complete packet must be received before the timer expires or an
error will be incurred.
Direct Access Number — F884
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Units — Seconds
Setting
Baud Rate
Parity
Stop Bits
0
2400
Odd
1
1
Even
2
None
3
4800
Odd
4
Even
5
None
6
9600
Odd
7
Even
8
None
9
19200
Odd
10
Even
11
None
12
38400
Odd
13
Even
14
None
15
2400
2
16
4800
17
9600
18
19200
19
38400
Note:
An improper parameter setting will result
in a Communication error.