100
Q9 ASD Installation and Operation Manual
Shaft Stationary
Program
Special Controls
This parameter Enables/Disables a continuous DC injection at half of the
amperage setting of
into a stopped motor. This feature is useful in preheating
the motor or to keep the rotor from spinning freely.
Shaft Stationary control starts after the DC injection brake stops the motor and
continues until ST – CC is opened, power is turned off, an Emergency Off
command is received, or this parameter is changed.
Enabling this feature will also require a non-zero entry at
.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F254
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
0 Hz Command Output
No Path — Direct Access Only
This parameter is used to set the go-to-zero method to be used by the ASD in the
event that the ASD is commanded to go to zero Hz.
Settings:
0 — Standard (DC Injection Braking)
1 — 0 Hz Command
Direct Access Number — F255
Parameter Type — Selection List
Factory Default — Standard (DC
Injection Braking)
Changeable During Run — No
Low Output Disable Time
Program
PID Setup
This parameter sets the time that the ASD is allowed to operate below the Lower-
Limit setting before an alarm and subsequent fault is incurred.
Direct Access Number — F256
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 600.0
Units — Seconds