82
Q9 ASD Installation and Operation Manual
V/f 5-Point Setting Frequency 5
No Path — Direct Access Only
The V/f 5-Point Setting Frequency 5 sets the frequency to be associated with the
voltage setting of parameter
(V/f 5-Point Setting Voltage 5).
and
for additional information on this setting.
Direct Access Number — F198
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (
Units — Hz
V/f 5-Point Setting Voltage 5
No Path — Direct Access Only
The V/f 5-Point Setting Voltage 5 establishes the output voltage level that is to
be associated with the frequency setting of
(V/f 5-Point Setting Frequency
5).
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
and
for additional information on this setting.
Direct Access Number — F199
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (
)
Frequency Priority Selection
Program
Frequency Settings
Either Frequency Mode 1 or Frequency Mode 2 may control the output
frequency of the ASD. This parameter determines which of the two will control
the output frequency and the conditions in which control will be switched from
one to the other.
Note:
Frequency Mode is abbreviated as FMOD.
Settings:
0 — FMOD Changed by Terminal Board (Frequency Mode)
1 — FMOD (
) (Frequency Mode)
The Frequency Mode 1 or Frequency Mode 2 selection specifies the source of
the input frequency command signal. These selections are performed at
, respectively.
If FMOD changed by Terminal Board is selected here, the ASD will follow the
control of the discrete input terminal assigned the function of Frequency
Priority. The discrete terminal Frequency Priority will toggle control to and
from Frequency Mode 1 and Frequency Mode 2 with each activation/
deactivation.
If FMOD (
) is selected here, the ASD will follow the control of the
Frequency Mode 1 setting for the duration that the commanded frequency of the
Frequency Mode 1 setting is greater than the setting of
If the commanded frequency of the Frequency Mode 1 setting is less than or
equal to the setting of
the ASD will follow the setting of Frequency Mode
2.
Direct Access Number — F200
Parameter Type — Selection List
Factory Default — FMOD (changed by
TB)
Changeable During Run — Yes