Q9 ASD Installation and Operation Manual
187
88
89
UP/DOWN Frequency
(UP) — Increases the speed of the motor for the duration of activation until reaching the
Upper-Limit setting or increases the speed of the motor in steps (see
for more information on this feature).
90
91
UP/DOWN Frequency
(DOWN) — Decreases the speed of the motor for the duration of activation until reaching the
Lower-Limit setting or decreases the speed of the motor in steps (see
for more information on this feature).
92
93
UP/DOWN Frequency
(CLEAR) — While operating in the Up/Down Frequency speed control mode this terminal
initiates a 0 Hz output command. If operating with an activated UP/DOWN Frequency (UP or DOWN) terminal, the
output goes to the Lower-Limit (
) setting.
98
99
Forward/Reverse
— This setting operates in conjunction with another terminal being set to the Run/Stop function.
When configured to Run (Run/Stop to CC), the make or break of this connection to CC changes the direction of the
motor.
100 101
Run/Stop
— This terminal enables the motor to run when activated and disables the motor when deactivated.
102 103
Line Bypass
— Initiates the ASD-to-Commercial Power switching function.
See parameter
for more information on this feature.
104 105
Frequency Priority
— Toggles frequency control to and from the settings of
and
with each activation/
deactivation.
106 107
V/I Terminal Priority
— Assigns Speed control to the V/I Terminal and overrides the
setting.
108 109
Terminal Priority
— Assigns Command control to the Terminal Board and overrides the
setting.
110 111
Edit Enable
— Allows for the override of the lockout parameter setting (
) allowing for parameter editing.
122 123
Fast Deceleration
— Using dynamic braking (if enabled and supported), stops the motor at the fastest rate allowed
by the load.
124 125
Pre-Excitation
— Applies an excitation current to the motor (holds shaft stationary) for the duration of the activation.
Note:
NO/NC = Normally Open/Normally Closed.
Table 4. (Continued) Discrete Input Terminal Assignment Selections and Descriptions.
Sel. No.
Terminal Selection Descriptions
NO NC
Summary of Contents for Q9 Series
Page 2: ......
Page 4: ......
Page 8: ......
Page 219: ...Q9 ASD Installation and Operation Manual 209 Figure 30 See Table 14 for Actual Dimensions ...