Q9 ASD Installation and Operation Manual
167
Ext. Comm. Cfg. 4
No Path — Direct Access Only
This parameter is read-only and is used to store and display the error codes that
correlate to the returned initialization status number (0 – 5).
The error codes are listed below along with their meaning:
0 — No Error (Normal Operation)
1 — Invalid Equipment
2 — Invalid Protocol
3 — Invalid Address
4 — Invalid Network Settings
5 — Resource Allocation Error
Direct Access Number — F885
Parameter Type — Numerical
Factory Default — No Error
Changeable During Run — Yes
Minimum — 0
Maximum — 255 (only 0 – 5 effective)
Ext. Comm. Cfg. 5 – 8
No Path — Direct Access Only
These parameters have protocol-specific functions. See the document ASD
NANOCOM ICC 10572-2.100-000 located at www.ICCDESIGNS.com for more
information on these parameter settings.
Direct Access Number — F886 - F889
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Network Option Reset Settings
Program
Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the targets of a Reset command received via the communications
link.
Settings:
0 — Reset ASD only
1 — Reset Option Board and ASD
Direct Access Number — F899
Parameter Type — Selection List
Factory Default — Reset ASD only
Changeable During Run — Yes
Input Function Target 1
Program
My Function Unit 1
This parameter plays a role in the setup of the My Function feature by selecting
the functionality of the programmable Input Function Target 1 terminal.
This setting assigns the function of the programmable Input Function Target 1
terminal to any of the user-selectable functions listed in
, or
.
From the listed tables select the corresponding Communications Number, Input
Setting, or Input Setting.
for more information on this parameter.
Direct Access Number — F900
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Input Function Command 1
Program
My Function Unit 1
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/reset function.
lists the available selections. Their use and selection
requirements are described in an example at
.
Direct Access Number — F901
Parameter Type — Selection List
Factory Default — 0 (NOP)