Q9 ASD Installation and Operation Manual
139
Backup Option Selection
No Path — Direct Access Only
This parameter sets the ASD disposition in the event that an Under-torque
condition exists for longer than the time setting of
Settings:
0 — Do Nothing
1 — Alarm
2 — Trip
Direct Access Number — F647
Parameter Type — Selection List
Factory Default — Do Nothing
Changeable During Run — No
Forced Fire Speed
Program
Special Controls
This parameter is used to enable the Forced Fire Speed function. The Forced
Fire Speed function runs
in the event of an emergency.
must be configured to use the Forced Fire Speed function.
Settings:
0 — Enabled
1 — Disabled
Direct Access Number — F650
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — No
Under-Torque at Constant Speed Disposition
No Path — Direct Access Only
This parameter sets the ASD disposition in the event that an Under-Torque
condition exists for longer than the time setting of
Settings:
0 — Do Nothing
1 — Alarm
2 — Trip
Direct Access Number — F651
Parameter Type — Selection List
Factory Default — Do Nothing
Changeable During Run — No
Under-Torque Level While ASD-Driven
No Path — Direct Access Only
and while the motor is being driven by the ASD,
this setting is used to set a low-torque threshold minimum level that must exist for
the duration of the time setting of parameter
disposition of the parameter
setting.
Direct Access Number — F652
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Under-Torque Level During Regeneration
No Path — Direct Access Only
When enabled at parameter
and during regeneration, this setting is used to
set a low-torque threshold minimum level that must exist for the duration of the
time setting of parameter
to activate the Under-Torque disposition of the
parameter
setting.
Direct Access Number — F653
Parameter Type — Selection List
Factory Default — Trip
Changeable During Run — No
Minimum — 0.00
Maximum — 250.0
Units — %
Fire Speed
Summary of Contents for Q9 Series
Page 2: ......
Page 4: ......
Page 8: ......
Page 219: ...Q9 ASD Installation and Operation Manual 209 Figure 30 See Table 14 for Actual Dimensions ...