162
Q9 ASD Installation and Operation Manual
Preset Speed Operation Selection
No Path — Direct Access Only
This parameter setting is used to set the Preset Speed selection to be used if
Preset Speed is selected at parameter
.
Settings:
0 — Disabled
1 – 15 — Preset Speed Number
Direct Access Number — F852
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Communications Option Station Address Monitor
No Path — Direct Access Only
This parameter is used in the setup of the communications network by reading the
Media Access Code (MAC) address of the ASD that is connected to a node of the
communications system.
The MAC Address is set via DIP switches of the optional device.
See the DeviceNet Option Instruction Manual (P/N 58683) for more information
on this parameter.
Direct Access Number — F853
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Communications Option Speed Switch Monitor DeviceNet/CC-
Link
No Path — Direct Access Only
—FUNCTION NOT AVAILABLE WITH THE Q9 ASD—
This parameter is used in the setup of the communications network by reading the
hardware-specific settings of the option card being used with the ASD.
If using the DEV002Z Devicenet card, this parameter reads the hardware switch
SW300 setting of the Devicenet card. SW300 sets the baud rate and the MAC
address of the option card that is connected to a node of the communications
system.
See the DeviceNet Option Instruction Manual (P/N 58683) for more information
on this parameter or see the instruction manual for the option being used with the
Q9 ASD.
Direct Access Number — F854
Parameter Type — Hardware Selectable
Factory Default — Option-Specific
Changeable During Run — No
Minimum — 0
Maximum — 255
Number of Poles of Motor
No Path — Direct Access Only
This parameter identifies the number of motor poles for the motor(s) being used.
Direct Access Number — F856
Parameter Type — Numerical
Factory Default — 4
Changeable During Run — No
Minimum — 2
Maximum — 16