Q9 ASD Installation and Operation Manual
103
UP/DOWN Frequency (UP) Response Time
No Path — Direct Access Only
This parameter functions in conjunction with the parameter settings of
,
. The purpose of these settings is to setup the ASD to
allow an externally-supplied discrete input signal to control the output frequency
of the ASD.
This method uses the discrete input terminal settings UP/DOWN Frequency
(UP) and UP/DOWN Frequency (DOWN) to change the ASD speed. Activation
of either terminal increases or decreases the output frequency at the Accel 1 or
Decel 1 rates, respectively.
Depending on the Delay setting, the UP/DOWN Frequency (UP/DOWN)
terminal may perform the increase/decrease function for the duration of the
activation or may act as a momentary contact that loads a new commanded
frequency upon activation.
In either case, to activate-and-hold will continue the up or down function until
reaching the Upper-Limit Frequency or the Lower-Limit Frequency,
respectively. At which point further activation will be ignored.
for more information on the UP/DOWN Frequency
function.
Setup Requirements
— Selects the Command control source; set to Terminal Block.
— Selects the Frequency Control Mode 1 control source; set to
UP/DOWN Frequency.
— Selects the Frequency Control Mode 2 control source: set to
UP/DOWN Frequency if used.
Set one unused discrete input terminal to UP/DOWN Frequency (UP) and one
unused discrete input terminal to UP/DOWN Frequency (DOWN).
— Sets the system-response delay to the initial activation of the discrete
input terminal UP/DOWN Frequency (UP). Also sets the response delay of
subsequent terminal activations of the UP/DOWN Frequency (UP) terminal
during an activate-and-hold.
—Sets the frequency increase amount for each activation of the UP/
DOWN Frequency (UP) terminal activation. The rate of the frequency
increase is set at Acceleration Time 1 (
— Sets the system-response delay to the initial activation of the discrete
input terminal UP/DOWN Frequency (DOWN). Also sets the activation delay
of subsequent terminal activations of the UP/DOWN Frequency (DOWN)
terminal during an activate-and-hold.
—Sets the frequency decrease amount for each activation of the UP/
DOWN Frequency (DOWN) terminal activation. The rate of the frequency
decrease is set at Deceleration Time 1 (
— At power up or after a reset, this parameter setting is used to provide a
starting frequency for the UP/DOWN Frequency function.
— At power down while running, and when enabled, this parameter
writes the running frequency into the
location and, upon a system restart,
uses this setting as the startup frequency.
Provide a Run command (F or R). The motor will run at the
setting.
Direct Access Number — F264
Parameter Type — Numerical
Factory Default — 0.1
Changeable During Run — Yes
Minimum — 0.0
Maximum — 10.0
Units — Seconds
Up/Down Frequency (UP) Mode
Up/Down Frequency (DOWN) Mode