Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 47/162
Operating manual - translation into English © thermofin GmbH
Picture 19
Editable from …to:
Measuring point 1: -50.00 … 20.00 °C
-60.00 … 70.00 °F
Correction value 1:
-10.00 … 10.00 dt°C
-20.00 … 20.00 dt°F
Measuring point 2: 20.00 … 60.00 °C
70.00 … 140.00 °F
Correction value 2:
-10.00 … 10.00 dt°C
-20.00 … 20.00 dt°F
Correction values for standard signals in %
Analogue voltage or current inputs (0-10 V, 2-10 V, 0-20 mA, 4-20 mA) are corrected as a
percentage.
Editable from -5.00 % to 5.00 %
Analogue OUT basic unit
Pressing the right arrow button enables the following functions to be selected:
Output
Terminal
Possible functions
AO – 1
(X4.34)
Speed circuit 1 (0-10 V)
Speed circuit 1 (2-10 V)
Wetting pump 1 speed (0-10 V)
Adiabatic valve 1 (2-10 V)
Not used
AO – 2
(X4.35)
Speed circuit 1 (0-10 V)
Speed circuit 2 (0-10 V)
Speed circuit 1 (2-10 V)
Speed circuit 2 (2-10 V)
Outlet temperature circuit 1 (-50 °C
0 V to +100 °C
10 V)
Adiabatic valve 1 (2-10 V)
Adiabatic valve 2 (2-10 V)
Low load level 1, 2-10 V
Wetting pump 1 speed (0-10 V)
Wetting pump 2 speed (0-10 V)