Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 124/162
Operating manual - translation into English © thermofin GmbH
Picture 90
Spray valves
The current switch-on and switch-off limits for the respective spray level are displayed in the
spray
valve [No]
submenu (see Picture 89). However, the spraying is only activated if the ambient
temperature limit (see 6.4.4 “
”) is exceeded. The following
parameters can be edited:
The value can be edited by selecting the buttons with a blue background.
Setpoint (SP) deviation Spraying ON
Switch-on condition for spray level [No]. This is fulfilled when the actual value is higher than
the setpoint by the percentage value set here. If all switch-on conditions are met, the respective
spray level switches ON.
Editable from … to:
0.0 … 20.0 %
Factory setting:
5.0 %
Setpoint (SP) deviation Spraying OFF
Switch-off condition for spray level [No]. This is fulfilled when the actual value is smaller or
larger than the setpoint by the percentage value set here (depending on the sign of the edited
value). If all switch-off conditions are met, the respective spray level switches OFF.