Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 53/162
Operating manual - translation into English © thermofin GmbH
Picture 27
The parameters required for this change depending on the type of fan control (see Picture 25). When
activating “Step switching” or “0 - 10 V DC”, various setting options are hidden and another is
displayed [see chapter 4.4.15
Control of the fans
The setpoint source of the fans is determined here. There are the following options to choose from:
Setpoint source
Explanation
Control of EBM Modbus*
Setpoint, status and fault messages are transmitted via Modbus. All
registers are written and read according to ebm-Papst
specifications. For setting the communication parameters, see
chapter 4.5 “
BMS (Building management system
Control of ZA Modbus
Setpoint, status and fault messages are transmitted via Modbus. All
registers are written and read according to Ziehl-Abegg
specifications. For setting the communication parameters, see
chapter 4.5 “
BMS (Building management system) bus system”.
Control of EBM Modbus
wireless
Setpoint, status and fault messages are transmitted via Modbus. All
registers are written and read according to ebm-Papst
specifications. The data transfer is realized by the TCS wireless
system instead of a signal cable. For setting the communication
parameters, see chapter 4.5 “
BMS (Building management system)