Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 89/162
Operating manual - translation into English © thermofin GmbH
Adjustable parameters:
Editable from ..to
Factory setting
Setpoint shifting NC – normal cooling max.
0 ... 50.0 °C
20.0 °C
0 ... 70.0 °F
20.0 °F
Setpoint shifting FC – free cooling max.
0 ... 20.0 °C
10.0 °C
0 ... 40.0 °F
10.0 °F
Setpoint shifting HR – heat recovery max.
0 ... 50.0 °C
20.0 °C
0 ... 70.0 °F
20.0 °F
Setpoint shifting via ambient temperature
Another option is the setpoint shifting via the outside air temperature. An outside air temperature
sensor is required for this. The TTS-90 temperature sensor is used as the sensor (see chapter 6.3.1
“
TTS temperature sensors
” in the device manual).
This function is limited to the setpoint for “Normal cooling” (NC). There is no setting option for
the setpoints for free cooling and heat recovery. Circuit 1 and 2 are also treated the same.
The shift value has the same effect on both circuits (see Picture 66).