Picture 89
Winter operation/Summer operation
The
winter operation
serves to protect all water-bearing parts from frost damage. Valve positions
are changed and water pipes are emptied during winter operation among other things. The use of
the spray functions is not possible in winter operation. When you select the “Winter operation” menu,
a submenu opens with the associated settings.
The settings can be edited by selecting the buttons with a blue background.
Winter operation ON <:
Temperature limit from which the device switches to winter
operation.
Editable from … to:
3.0 … 30.0 °C
Factory setting:
3.0 °C
Winter operation OFF >:
Temperature limit from which the device switches to summer
operation (winter operation deactivated). The switch-off
temperature must be at least 1 °C above the switch-on
temperature.
Editable from … to:
4.0 … 40.0 °C
Factory setting:
10.0 °C
RPM Winter operation OFF:
Another switch-off condition that switches off winter operation
from a certain speed (in %).