Control (activation)
Basically, the following steps must be observed for activating this function:
1. Set digital input (DI-6) to “Spray pump fault” (see also chapter 5.2.1 “
Logical “high” (+24 V DC at the input)
≙
Pump OK
Logical “low” (0 V DC at the input)
≙
Pump fault
For example for motor protection
2. Set digital output (DO-6) to “Spray pump” (see also chapter 5.2.2 “
Logical “high” (+24 V DC at the output)
≙
Spray pump requirement
Logical “low” (0 V DC at the output)
≙
No requirement
3. A type of control must be selected. There are the following options (see also chapter 4.2.12
Spray pump control “internal”
If the release (requirement circuit 1, DI-1) is set and the conditions in the “Spray pump”
menu are met, the pump switches on.
- See below (under
B
) all switch-on and switch-off conditions.
Spray pump control “via terminal”
- There is currently no digital input specifically dedicated to activating the spray pump.
- As with “internal”, the pump is also switched on and off via the release (external
requirement, DI-1) and the conditions in the menu (see
B
).
Spray pump control “via BUS”
-
as soon as the below-mentioned bit is set and the
conditions in the “Spray pump” menu are met, the pump switches on.
- The following values apply to direct communication via MODBUS:
Register Bit
Designation
Meaning
Register
value
2
1
Spray pump
TRUE = Spray pump 1
Writing
2
143
9
“Spray pump”
Feedback
TRUE = Spray pump 1 active
Reading
512