M10 W Tray sensor wire
break
- The resistance at the analogue
input does not correspond to a
suitable tray sensor
- Resistance is clearly too high
- Incorrect configuration of the
analogue input (jumper position)
- Sensor line interrupted / check
wiring
- Check terminal points
- Check the configuration of the
respective analogue input (see
device manual, chapter 3.6.4)
- Replace the tray sensor
- The analogue input may be
defective, please contact the
manufacturer
151 2
M11 W Tray sensor short
circuit
- The resistance at the analogue
input does not correspond to a
suitable tray sensor
- Resistance is clearly too low
- Incorrect configuration of the
analogue input (jumper position)
- Sensor line is short-circuited /
check wiring
- Check terminal points
- Check the configuration of the
respective analogue input (see
device manual, chapter 3.6.4)
- Replace the tray sensor
- The analogue input may be
defective, please contact the
manufacturer
151 3
M12 W
Cell sensor wire
break
- The resistance at the analogue
input does not correspond to a
suitable cell sensor
- Resistance is clearly too high
- Incorrect configuration of the
analogue input (jumper position)
- Sensor line interrupted / check
wiring
- Check terminal points
- Check the configuration of the
respective analogue input (see
device manual, chapter 3.6.4)
- Replace the cell sensor
- The analogue input may be
defective, please contact the
manufacturer
151 4
M13 W Cell sensor short
circuit
- The resistance at the analogue
input does not correspond to a
suitable cell sensor
- Resistance is clearly too low
- Incorrect configuration of the
analogue input (jumper position)
- Sensor line is short-circuited /
check wiring
- Check terminal points
- Check the configuration of the
respective analogue input (see
device manual, chapter 3.6.4)
- Replace the cell sensor
- The analogue input may be
defective, please contact the
manufacturer
151 5
M14 W Humidity sensor
wire break
- A current < 4mA flows at the
corresponding analogue input
-This does not correspond to a
suitable humidity sensor (4-
20mA)
- Resistance is clearly too high
- Incorrect configuration of the
analogue input (jumper position)
- Sensor line interrupted / check
wiring
- Check terminal points
- Check the configuration of the
respective analogue input (see
device manual, chapter 3.6.4)
- Replace the humidity sensor
- The analogue input may be
defective, please contact the
manufacturer
151 15