Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 136/162
Operating manual - translation into English © thermofin GmbH
BUS parameter valves
Feedback via Modbus:
Register Bit
Designation
Meaning
Register
value
144
0
Main water valve open
TRUE = Main water valve open
Reading
1
145
0
V01 Main water valve
runtime error
TRUE = Main water valve runtime
error
Reading
1
144
1
Drain valve open
TRUE = Drain valve open
Reading
2
145
1
V02 Drain valve
runtime error
TRUE = Drain valve runtime error
Reading
2
144
6
Vent valve open
TRUE = Vent valve open
Reading
64
145
6
V03 Vent valve runtime
error
TRUE = Vent valve runtime error
Reading
64
Register Bit
Designation
Meaning
Register
value/typ
e
Output
10
-
Control valve 1
Control valve control value
circuit 1
INT
0 … 1000
Writing
0.0 … 100.0 %
91
-
Setpoint
WORD
Reading
0 … 100%
92
-
Actual value
WORD
Reading
0 … 100 %
145
9
V09 Control valve
1 Position error
TRUE = Control valve adiab.
pads, position error circuit 1
Reading
512
-
152
0
V08 Control valve
1 wire break
TRUE = Control valve adiab.
pads, wire break circuit 1
Reading
1
-
11
-
Control valve 2
Control valve control value
circuit 2
INT
0 … 1000
Writing
0.0 … 100.0 %
93
-
Setpoint
WORD
Reading
0 … 100 %
94
-
Actual value
WORD
Reading
0 … 100 %
145
10
V09 Control valve
2 Position error
TRUE = Control valve adiab.
pads, position error circuit 2
Reading
1024
-
152
1
V08 Control valve
2 wire break
TRUE = Control valve adiab.
pads, wire break circuit 2
Reading
2
-