Picture 59
Picture 60
As a result, output 1 is switched on again and another fault can be sent via it again without the first
cause of the fault having to be eliminated.
A first unimportant fault does not prevent the new report of a further, possibly existential, later
occurring fault report through this switching.
This acknowledgement process can be repeated several times without restriction. In addition, all
individual faults with text, time and date are recorded in the alarm history in a voltage failure-
safe manner. (see chapter 5.4.2 “
It goes without saying that the messages via outputs 1 and 2 are independent of any existing
connection to a control room via a data bus to the TCS.2.
Fan Operating data / Status
This function
in the “Alarms” menu can only be selected if the installed fans are controlled
via MODBUS. Only then the electronics report all details of the following windows back to the
TCS.2.
This window provides a general overview of the
fan operating data.
All faulty fans are displayed with a red box at the
bottom left of the window. (White -> fan OK, red -
> fan error) In this example, all 24 fans are
currently malfunctioning. A maximum of 240 fans
can be displayed.
One level deeper
the detailed cause of the fan
fault and the associated error code can be read
out. Here in the example F18 has a red
background.
In order to display the status of the faulty fan, the
corresponding number must be entered at the top
right. (See picture ...)