Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 133/162
Operating manual - translation into English © thermofin GmbH
Register Bit
Designation
Meaning
Register
value
144
7
Pressure increase
requirement
TRUE = Pressure increase requirement
Reading
128
145
7
Pressure increase
fault
TRUE = Pressure increase fault
Reading
128
Fresh water meter
After activating the
fresh water meter
function, the pulses are counted at the corresponding digital
input (1 pulse/litre) and the amount of water used is displayed by the TCS.2 in litres and m³ (see also
chapter 5.3 “
”). The following inputs are used:
Digital input DI-6 or DI-7
(“Fresh water meter”)
See also chapter 4.3.1 “
Impulse requirement: + 24 V DC
≥
50 ms
Messages via BUS
The following values are output via the BUS:
Register Word
Designation
Meaning
Register
value
81
HI
Fresh water
consumption
Fresh water consumption in m³
Cubic meter
82
LO
Cooling mat system
The user can access the
cooling mat system
submenu by pressing the mat symbol (see Picture
96). If the main water valve is open, the symbol is highlighted in light blue. It thus shows whether the
adiabatic mats are in operation.