Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 116/162
Operating manual - translation into English © thermofin GmbH
Storage container
After activating the storage
container function
, the level of a water storage container for the
spraying system is monitored via the TCS.2. The following I/Os are used for input and output:
Digital input DI-7 or DI-8
[“RM (feedback) storage container”]
After activating this function, the input must be “true”, otherwise the TCS issues an error
message “S06 storage container fault”.
See also chapter 4.3.1 “
Digital output DO-7 or DO-8
(“Storage container requirement”)
These outputs are set permanently in summer operation (winter operation deactivated).
They signal a possible water requirement of the spray system.
See also chapter 4.3.2 “
Messages via BUS
The following status messages are output via the BUS
Register Bit
Designation
Meaning
Register
value
144
8
Storage container
requirement
TRUE = Storage container requirement
Reading
256
145
8
Storage container
fault
TRUE = Storage container fault
Reading
256
Pressure increase
After activating the
pressure increase
function, the pump(s) for the spraying system are monitored
via the TCS.2. The following I/Os are used for input and output:
Digital input DI-8
[“RM (feedback) pressure increase”]
After activating this function, the input must be “true”, otherwise the TCS issues an error
message “S07 pressure increase fault”.
See also chapter 4.3.1 “
Digital output DO-8
(“Pressure increase requirement”)
This output is set as soon as a wet level (spray level) is active.
See also chapter 4.3.2 “
Messages via BUS
The following status messages are output via the BUS: