This function is activated in the Device settings ->
Control (see chapter 4.2.4 “
. If “via
AT” is selected, the “Setpoint shifting” button in the
Setpoints menu has a blue background and can
be pressed. The user gets to the following settings
window: (Picture 65)
①
“Setpoint shift ambient temperature max”:
The value edited here is added to the setpoint when the ambient temperature rises. How much the
ambient temperature has to rise for this maximum value depends on the shift factor
③
.
②
“Setpoint start point ambient temperature“:
Ambient temperature value at which the setpoint shift starts. The setpoint remains unchanged below
this temperature.
③
“Setpoint shift factor ambient temperature”:
The shift factor quantifies the shift effect per Kelvin change in the ambient air temperature. With a
factor of 1.0, the setpoint is shifted by 1K when the ambient air temperature is increased by 1K.
④
“Setpoint”:
Set target temperature of circuit 1 (25 °C) and circuit 2 (30 °C)
⑤
“Shift value”:
①
②
③