Operating manual - translation into English © thermofin GmbH
Setpoint shift control
This function enables the operator to adapt the condensing pressure or the outlet temperature to
specific operating conditions. All relevant values are set in the
Main menu
Setpoints
Setpoint
shifting.
This menu item is only displayed after a control has been selected (see also chapter 5.6.3
The following control options are available:
Signal type:
Analogue
0 – 100 %
Options:
Off *
Function deactivated.
Via terminal
0 – 10 V
0 - 10 V signal at terminal X4.31 (AI-3) or X4.32
(AI-4) for two-circuit devices, see chapter 1.4
(circuit diagram TCS.2)
Via terminal
2 – 10 V
2 - 10 V signal at terminal X4.31 (AI-3) or X4.32
(AI-4) for two-circuit devices, see chapter 1.4
(circuit diagram TCS.2)
Via terminal
0 – 20 mA
0 - 20 V signal at terminal X4.31 (AI-3) or X4.32
(AI-4) for two-circuit devices, see chapter 1.4
(circuit diagram TCS.2)
Via terminal
4 – 20 mA
4 - 20 V signal at terminal X4.31 (AI-3) or X4.32
(AI-4) for two-circuit devices, see chapter 1.4
(circuit diagram TCS.2)
Via AT (ambient
temperature)
The shift starts to raise the setpoint at a certain
ambient temperature.
All relevant values can be set in the
Main
menu
Setpoints
“
Setpoint shifting
” (see
also chapter 5.6.3 “
)
Via bus
The type of communication bus is set in the
Device settings
BMS bus system
[see also
chapter “4.5
”].
The following parameters apply to direct
communication via MODBUS:
Circuit 1:
Register 4 (INT), (register value: -250 to 250
-25,0°C to +25,0°C or -450 to +450
for
-45,0°F to +45,0°F)
Circuit 2:
Register 5 (INT), (register value: -250 to 250
-25,0°C to +25,0°C or -450 to +450
for
-45,0°F to +45,0°F)
* Factory setting