Specifications
3-4
DRIVE SYSTEM
NOTE: Use belt tension gauge TK P/N 204-427 whenever possible to check belt tension. However, on
some unit models, and on some belts, it is difficult to use the gauge. Adjust these belts to allow 12 mm
of deflection at the centre of the longest span. New belts should be tensioned cold and tensioned cold
again after 10 hours of unit operation.
Belt
Tension Number on TK Gauge
204-427
Field Reset
New TK Gauge 204-1903
Field Reset
SL: Direct Drive to Compressor (Model 30)
Electric Motor/Compressor Drive—Double
V Belt (Model 50)
80
37 Ampere, 12 Vdc Alternator
30
65 or 120 Ampere, 12 Vdc Alternator
45
Water Pump
35-40
Upper Fan (Fan to Jackshaft)
75
Lower Fan (Engine to Jackshaft) w/37
Ampere Alternator
80
Lower Fan (Engine to Jackshaft) w/65 or 120
Ampere Alternator
85
SLe and SPECTRUM SL**: Direct Drive to Compressor (Model 30)
Frequency
Electric Motor/Compressor Drive—
80–85
Upper Fan (Fan to Jackshaft)
85–90
Lower Fan (Engine to Jackshaft) w/37
Ampere Alternator
85–90
TK Gauge 204-1903
Tension Number on TK Gauge
204-427
Field Reset
New Belt
Frequency (Hz)
Field Reset
Frequency (Hz)
SLX/SLXe/SLXi and SLX/SLXe/SLXi
SPECTRUM **: Direct Drive to Compressor
(Model 30)
Electric Motor/Compressor Drive:
Units fitted with original SLX clutch
tensioner (up until build date 13th August
2013)
73-76
67-72
Units fitted with SLX clutch tensioner
retrofit (service P/N: 78-1884)
NB: use service tool (part number:
204-2436) to set belt tension.
Distance of 139.0mm as set by
service tool equates to 78-81 Hz
for a new belt, and 69-73 Hz for a
field reset belt
Units fitted with SLXe/SLXi clutch
tensioner (service P/N: 77-3189)
NB: use service tool (part number:
204-2436) to set belt tension.
Distance of 139.0mm as set by
service tool equates to 95 Hz for a
new belt
Fan Drive Belt (Model 50):
Fan Drive Belt
106-118
95-108
Water Pump
35-40
** SLe, SPECTRUM SL, SLX, SLXe, SLXi and SLX/SLXe/SLXi SPECTRUM units have one/two automatic tensioning
fan drive belt systems, in order to drive the compressor and the evaporator fanshaft. SLX/SLXe only has one, SL has two
(Upper and Lower).
The lower polygroove belt runs from the engine/compressor to the intermediate jackshaft (or electric motor, depending on
the unit model).
The upper polygroove belt links the intermediate jackshaft to the evaporator fanshaft, incorporating other belt driven
components such as the condenser blowers and the alternator.
Summary of Contents for SLXi Spectrum
Page 17: ...Safety Precautions 2 5 Warning Decals...
Page 18: ...Safety Precautions 2 6 Warning Decals Information Decals...
Page 74: ...Unit Description 5 30...
Page 128: ...Controller Operation 7 28...
Page 156: ...Electrical Maintenance 8 28...
Page 234: ...Refrigeration Maintenance 10 22...
Page 309: ...13 Mechanical Diagnosis TK 482 TK 486 and TK 486V Engines 13 2...
Page 316: ...Mechanical Diagnosis 13 8...
Page 322: ...Refrigeration System Diagnosis 14 6...
Page 332: ...Single Temperature Refrigeration System Diagrams 15 10...
Page 339: ...Multi Temperature Refrigeration System Diagrams 16 7...
Page 340: ...Multi Temperature Refrigeration System Diagrams 16 8...