Unit Description
5-8
When a Defrost cycle is initiated, the defrost relay energises the damper motor, pilot solenoid and heater contactor (during electric
standby operation on Model 50 units with optional electric heaters). If the unit is in Null mode on CYCLE-SENTRY or Electric
Standby operation, pressing the manual defrost key will initiate a manual defrost. The unit remains on Defrost until the evaporator
coil temperature increases to 14 C, at which time, the unit shifts back to the operating mode required by controller demand.
NOTE: If the controller calls for the Null mode (CYCLE-SENTRY or Electric Standby operation) while the unit is defrosting,
the unit will continue to operate until defrosting is complete. Then the unit will stop.
Center or Rear Evaporator (Basic system on
Continuous Run or CYCLE-SENTRY Engine
Operation)
1.
Setpoint
2.
Temperature Decrease
3.
Temperature Increase
A.
Cool
B.
Null
C.
Heat
1
Summary of Contents for SLXi Spectrum
Page 17: ...Safety Precautions 2 5 Warning Decals...
Page 18: ...Safety Precautions 2 6 Warning Decals Information Decals...
Page 74: ...Unit Description 5 30...
Page 128: ...Controller Operation 7 28...
Page 156: ...Electrical Maintenance 8 28...
Page 234: ...Refrigeration Maintenance 10 22...
Page 309: ...13 Mechanical Diagnosis TK 482 TK 486 and TK 486V Engines 13 2...
Page 316: ...Mechanical Diagnosis 13 8...
Page 322: ...Refrigeration System Diagnosis 14 6...
Page 332: ...Single Temperature Refrigeration System Diagrams 15 10...
Page 339: ...Multi Temperature Refrigeration System Diagrams 16 7...
Page 340: ...Multi Temperature Refrigeration System Diagrams 16 8...