76
Remote Control
MEAS_EN1V - 0x01 - Energize at 1V
MEAS_EN10V - 0x0A - Energize at 10V
MEAS_EN40V - 0x28 - Energize at 40V
MEAS_EN100V
- 0x64 - Energize at 100V
MEAS_EN10VCT
- 0xFF - Energize at 10V for CT
Returns:
+OK:~: - The configuration and voltage were set successfully
+ERROR:090A:~: - The voltage was invalid
+ERROR:0911:~: - The specified configuration was bad
Comments:
The user should allow the system to stabilize before making any measurements.
Setup:Querycurrentsetup
This returns the current gain, configuration and voltage set for the instrument.
Structure:
+S:Q:~:
Returns:
+OK:<Gain>:<Configuration>:<Voltage>:~:
<Gain> (integer) is the system gain
<Configuration> (integer) is the system configuration
<Voltage> (integer) is the system output voltage
Comments:
The values returned for <Gain>, <Configuration> and <voltage> can be determined
from the constants defined for the Setup:SetGain and Setup:SetConfiguration functions.
Setup:GetRawMeterReadings
This returns the current raw (unprocessed) meter readings and measurement status.
Structure:
+S:M:~:
Returns:
+OK:<PriV>:<SecV>:<PriI>:<Status>:~:
<PriV> (integer) is the primary voltage magnitude
<SecV> (integer) is the secondary voltage magnitude
<PriI> (integer) is the primary current magnitude
<Status> (integer) is the current status of the measurement system. The lowest 8
bits
onstitute a rolling counter. This is updated each time a new meter reading is taken -
by
checking this rolling counter, the user can determine whether the meter readings
have
updated since last time they were read.
The upper bits carry status information for the metering system as follows:
MEAS_PVOR D10 (0x0800)
- Primary Voltage Overrange
MEAS_SVOR D12 (0x1000)
- Sec. Voltage Overrange
MEAS_RANGE D13 (0x2000)
- System Autoranging
MEAS_VFAIL D14 (0x4000)
- Output voltage fail
MEAS_MATOK D15 (0x8000)
- Switching Matrix Stable
Comments:
None
Setup:ReadCalFactors
This reads the calibration factors from the EEPROM, so they can be backed up.
Structure:
+S:R:<Index>:~:
Fields:
<Index> is the index number in the EEPROM to be read. This is one of:
0
Pri. Volts. Range 1, Sec. Volts. Range 1
Summary of Contents for TTR 2795
Page 1: ...Operating Instructions HAEFELY TEST AG TTR 2795 Transformer Turns Ratio Meter Version 1 4 ...
Page 10: ...6 Introduction Maximum Roll Diameter Outer 50mm Inner 10mm ...
Page 22: ...18 Connection and Setup Figure 11 Connecting to three phase BCT ...
Page 101: ...Application Software APSW 2795 97 ...
Page 111: ...Miscellaneous 107 14 7 Conformity ...