20
Connection and Setup
Note for the transformer configuration look up tables:
The “HV Connect” and “LV Connect” give the basic configuration for measuring the transformer to determine the turns
ratio (TR). The actual applied configuration depends on the phase rotation of the transformer (see the “Phase
Displacement” Info line)
Example: Dyn11 Transformer, HV-LV: 150kV-50kV,
N
HV
: 520 turns, N
LV
: 100 turns
TR = N
HV
/ N
L V
= 520 / 100 = 5.2
(=>VR*
√
3=3*
√
3=5.2).
VR = 150/50 = 3.
TR
Turns Ratio
VR
Voltage Ratio
NHV Number of HV-windings
NLV Number of LV-windings