62
Remote Control
+ERROR:0300:~:
- No update - test running
Comments:
If the tap definition is invalid (more than 40 taps selected or bottom tap out of the
range +/-128 or the nominal tap out of range) the system returns an invalid response with the original settings. Also
the step percent or step voltage, whichever is applicable is checked for validity. The requested settings are ignored
unless all the above are valid.
In cases where there are one tap or more and the tapsetup field is HV or LV, the system updates the individual tap
voltages, based on the step value and the LV or HV nominal voltage of the setup memory.
Test:Setup:NominalTapVoltage
This sets the primary and secondary voltages for the nominal tap.
Structure:
+T:S:N:<HV Nominal Voltage>:<LV Nominal Voltage>:~:
Fields:
<HV Voltage> (float) is the voltage for the HV side of the nominal tap.
This is entered in units of kV.
<LV Voltage> (float) is the voltage for the LV side of nominal tap.
Returns
:
+OK:~:
- Nominal Tap voltages set OK
+ERROR:0300:~:
- No update - test running
Comments:
There is no checking performed on the HV and LV voltages.
Test:Setup:IndividualTap
This sets the primary and secondary voltages for the individual tap to be measured.
Structure:
+T:S:I:<TapNo>:<HV Voltage>:<LV Voltage>:~:
Fields:
<TapNo> (integer) is the number of the tap being set. This is in the range 0 to
<NumTaps>. If a value outside this range is entered, the system will generate an error
<HV Voltage> (float) is the boilerplate voltage for the HV side of the tap being set.
This is entered in units of kV.
<LV Voltage> (float) is the boilerplate voltage for the LV side of the tap being set .
Returns
:
+OK:~:
- Tap voltages set OK
+ERROR:0902:~:
- Working Memory has data
+ERROR:0907:~:
- Tap No is invalid.
+ERROR:0300:~:
- No update - test running
Comments:
The function will return an error if the tap number is outside the range 0 to
<TapNo>. There is no checking performed on the HV and LV voltages.
Test:Info:Serial
This sets up the serial number of the unit
Structure:
+T:I:S:<Serial No>:~:
Fields:
<Serial No> (string) is a 20 character unit identification string.
Returns:
+OK:~: - The Serial number has been updated.
+ERROR:0902:~:
- Working Memory has data
+ERROR:0300:~:
- No update - test running
Comments:
If a string longer than 20 characters is received it is truncated to 20 characters (plus
terminating null).
Summary of Contents for TTR 2795
Page 1: ...Operating Instructions HAEFELY TEST AG TTR 2795 Transformer Turns Ratio Meter Version 1 4 ...
Page 10: ...6 Introduction Maximum Roll Diameter Outer 50mm Inner 10mm ...
Page 22: ...18 Connection and Setup Figure 11 Connecting to three phase BCT ...
Page 101: ...Application Software APSW 2795 97 ...
Page 111: ...Miscellaneous 107 14 7 Conformity ...