64
Remote Control
Test:Measure:Run
This runs the measurement procedure.
Structure:
+T:M:R:~:
Fields:
None
Returns
:
+OK:~: - Measurement Sequence running
+ERROR:090C:~: - Measurement sequence already running
+ERROR:090D:~: - Unable to run measurement sequence
Comments
:
The system will report that it is unable to run if the parameters are not set correctly
or it has determined there is a fault with the unit.
Test:Measure:Halt
This halts the measurement sequence
Structure:
+T:M:H:~:
Fields:
None
Returns
:
+OK:Y:~: - Measurement Sequence is being halted
+OK:H:~: - Measurement sequence already halted.
Comments:
None
Test:Measure:Query
This returns the current state of the measurement system, and the last results gathered.
Structure:
+T:M:Q:~:
Fields:
None
Returns
:
+OK:<State>:<VectorGroup>:<Voltage>:<TapNo>:~:
<State> (integer) - current state of the measurement system. The value returned
will be
one of the following:
TS_IDLE (0x00) - Test system is not running a test
TS_CONN (0x01) - Test system checking for correct connection.
TS_CONFIG (0x02) - Test system checking configuration
TS_DISP (0x03) - Test system measuring phase displacement
TS_MEAS (0x04) - Test system measuring ratio
TS_TAPWAIT(0x05) - System waiting to test next tap
TS_SYS (0x06) - Checking System Integrity
TS_VOLT (0x07) - Determining test voltage
TS_FIVDLFT (0xF8) – Floating input voltage detected
TS_USDATAFLT (0xF9) - Unsaved Data in working memory
TS_NOMEMFLT (0xFA) - No memory to save results In
TS_ESFLT (0xFB) - Emergency stop pressed
TS_IFLT (0xFC) - Excessive current draw fault
TS_OORFLT (0xFD) - Out of Measurement Range
TS_CFGFLT (0xFE) - Configuration setup fault
TS_REVFLT (0xFF) - HV-LV connection reversal
<VectorGroup> (Integer) - vector group of the transformer. If automatic
configuration
detection is completed, it will hold the transformer configuration. It the phase
displacement
has been measured, it will hold the measured phase displacement.
<Voltage> (integer) the test voltage used for the measurement
<TapNo> (integer) the current tap being measured (0..<NumTaps>)
Summary of Contents for TTR 2795
Page 1: ...Operating Instructions HAEFELY TEST AG TTR 2795 Transformer Turns Ratio Meter Version 1 4 ...
Page 10: ...6 Introduction Maximum Roll Diameter Outer 50mm Inner 10mm ...
Page 22: ...18 Connection and Setup Figure 11 Connecting to three phase BCT ...
Page 101: ...Application Software APSW 2795 97 ...
Page 111: ...Miscellaneous 107 14 7 Conformity ...