Memory Functions
53
It indicates the date and time the test was performed, whether it is a test or a setup and the number of the memory it
is stored in. Beneath that it shows the basic setup information for the stored in the memory
Configuration YYn0
Test Voltage 100V
HV Nom Voltage 9.00kV
LV Nom Voltage 1.00kV
Total Taps 0
Bot Tap Number 0
Nom Tap Number 0
Step Tap-Tap 0.5kV
Max Deviation 0.05%
DUT Serial No 12345678
DUT Type 87654321
DUT Location xyz
Operator F. Bloggs
If the contents of the memory is a test, the configuration is shown as above as a complete definition . If the memory is
a setup, the configuration is split up into Primary configuration, secondary configuration and phase displacement. If
the primary configuration is set to “
Auto 3ph
”, “
Single
” or “
CT
” then the secondary configuration and phase
displacement Fields: are not shown.
For a test memory, beneath the basic setup information, the display shows the test configuration for each of the
phases tested:
Phase Descr. : A H1-(H2H3):X1-(X2X3)
B H2-(H1H3):X2-(X1X3)
C H3-(H1H2):X3-(X1X2)
Underneath that it displays the results for each tap
Tap: 0 (1 of 5)
HV: 9.00kV LV: 1.00kV
---------------------------------------
Phase T-Ratio TRDev PhDev Current
A 9.0136 0.15 0.2
°
38mA
B 9.0135 0.15 0.4
°
42mA
C 9.0136 0.15 0.1
°
32mA
If the memory holds information on a tapped transformer pressing the “
View Tap
” button will display the nominal HV
and LV voltages set for the transformer
Summary of Contents for TTR 2795
Page 1: ...Operating Instructions HAEFELY TEST AG TTR 2795 Transformer Turns Ratio Meter Version 1 4 ...
Page 10: ...6 Introduction Maximum Roll Diameter Outer 50mm Inner 10mm ...
Page 22: ...18 Connection and Setup Figure 11 Connecting to three phase BCT ...
Page 101: ...Application Software APSW 2795 97 ...
Page 111: ...Miscellaneous 107 14 7 Conformity ...