48
Running A Test
If a transformer with irregularly spaced taps is being tested and the measurement of
deviation is being performed, it is imperative that the taps are set up on the transformer in
the same sequence they are defined in the test setup otherwise the deviation will be
calculated incorrectly.
If a transformer with regularly spaced taps is being tested, the test should start from the
lowest output tap and work upwards otherwise the deviation will not be calculated correctly.
8.5
Testing A Tapped Transformer using the
Tap Changer Button
When testing large transformers with tap changers, it can be awkward to place the TTR where it can be conveniently
operated at the same time as the tap changer system. Tettex supply an optional control button that connects to the
system via the Tap Changer socket on the front panel.
The test is started from the front panel in the normal way. When the connection check, configuration determination
and phase displacement determination is complete, the system will bleep once and the light in the tap changer button
will light. The user can then go to the tap changer controls and set the required tap. Once the tap is in place, the
button is pressed to start the test for that tap. The lamp on the button will extinguish while the test is in process. Once
the test for that tap is finished, the lamp will illuminate again to indicate that the tap can be changed. When the tap is
set the user presses the button to perform the test.
The instrument takes approximately 20 seconds to measure a three phase transformer, if the button does not
illuminate to indicate the system is ready to start the next stage, either the test has completed or there has been a
fault.
8.6
Options When the Test has Completed
When the test has completed, the system provides a number of options for reviewing and handling the data that has
been recorded. The options are spread over two menus, which are switched between using the “MORE >” button.
The options are:
UP
This moves the system back to the top-level menu
SAVE
Saves the test result into the system memory.
Prints a test report on the internal printer
MORE >
Switches between the two menus
RESTART
Runs the test procedure again.
GRAPH
This option is only available when a tapped transformer has been tested. It displays
the results of the test in graphical rather than tabular form.
8.7
Saving the Test Results
When “
SAVE
” is pressed, the test results are saved into the next available memory location on the system. This is
indicated on the screen using a message box. Press “
OK
” to return to the test menu.
Summary of Contents for TTR 2795
Page 1: ...Operating Instructions HAEFELY TEST AG TTR 2795 Transformer Turns Ratio Meter Version 1 4 ...
Page 10: ...6 Introduction Maximum Roll Diameter Outer 50mm Inner 10mm ...
Page 22: ...18 Connection and Setup Figure 11 Connecting to three phase BCT ...
Page 101: ...Application Software APSW 2795 97 ...
Page 111: ...Miscellaneous 107 14 7 Conformity ...