83-530-000 Rev G
64
4
Over Voltage
OVP
5
Shut Off
SO
6
Output Off
OFF
7(MSB)
Enable
ENA
3. Status Enable register
The Status Enable Register is set by the user to enable SRQs from changes in power supply status.
Table 7-14: Status Enable Register
BIT
Status name
Status symbol
Bit Set condition
Bit reset condition
0 (LSB)
Constant Voltage
CV
1
Constant Current
CC
2
No Fault
NFLT
3
Fault active
FLT
User command:
“SENA nn” is
received, where
nn is hexadecimal
bits.
User command: “SENA nn”
is received, where nn is
hexadecimal bits.
If “nn”=00, no SRQ is sent
when there is a change in
Status Condition Register.
4
Auto-Restart enabled
AST
Always zero
Always zero
5
Fold enabled
FDE
Always zero
Always zero
6
Spare
Spare
Always zero
Always zero
7 (MSB)
Local Mode
LCL
“SENA nn”
command
“SENA nn”
command
4. Status Event Register
The Status Event Register will set a bit if a change in the power supply status occurs and it is enabled.
The register is cleared when the “SEVE?” or “CLS” commands are received. A change in this register
will generate SRQ.
Table 7-15: Status Event Register
BIT
Status name
Status symbol
Bit Set condition
Bit reset condition
0 (LSB)
Constant Voltage
CV
1
Constant Current
CC
2
No Fault
NFLT
3
Fault active
FLT
Changes in status
occurs and it is
enabled.
The change can
set a bit, but when
the change clears
the bit remains
4
Auto-Restart enabled
0
Always zero
5
Fold enabled
0
Always zero
6
Spare
0
Always zero
Entire Event Register is
cleared when user sends
“SEVE?” command to read
the register.
“CLS” and power-up also
clear the Status Event
Register.
Summary of Contents for GENESYS 10KW
Page 2: ......
Page 3: ......
Page 31: ...83 530 000 Rev G 28 Fig 4 2 Rear panel connections and controls...