83-530-000 Rev G
16
Input Terminal Block
with cover.
Input Terminal Block
Input Rating
Label
NOTE: The figure shows input
connection from left side.
For connection from right side
reverse the input cover.
Figure 3.1
3.7.1 Recommended Cable Size for Input Connection
INPUT VOLTAGE
CURRENT RMS AMPS
PER PHASE
RECOMMENDED
COPPER WIRE SIZE
208
75
4 AWG
400
45
6 AWG
480
35
7 AWG
The AC input current and voltage rating is marked on the rear terminal of the power supply.
The Protective Earth Ground
must be connected
before applying AC Line Power to the power supply.