STULZ CyberRow Chilled Water Series Installation, Operation & Maintenance Manual
(
Dec.
, 2013)
4-50
BMS
Address
Modbus
Address
BACnet
Address
Description
Default
Direction
18 019
18
Inverter
status
0
R/W
19 020
19
Autotuning
status
0
R/W
20 021
20
Emergency
shutdown
0 R
21 022
21
Remote
shutdown
0 R
22
023
22
Customer alarm 1
0
R
23 024
23
Airfl ow alarm
0
R
24 025
24
Filter
alarm
0 R
25 026
25
Fire/Smoke
alarm
0 R
26
027
26
Water detection alarm
0
R
27
028
27
Motor overload status
0
R/W
28
029
28
Condensate pan alarm
0
R
29
030
29
Circuit1 low pressure alarm
0
R
30
031
30
Circuit1 high pressure alarm
0
R
31
032
31
Power supply status
0
R/W
32 033
32
Drive
alarm
0
R/W
33 034
33
Pump
alarm
0 R
34
035
34
Dual power input A alarm
0
R
35
036
35
Dual power input B alarm
0
R
36
037
36
Customer alarm 2
0
R
37
038
37
Customer alarm 3
0
R
38 039
38
Humidifi er alarm
0
R
39
040
39
Flow temp sensors CW1 alarm
0
R
40
041
40
Alarm off-line power+
0
R
41
042
41
Upper Fan alarm
0
R
42
043
42
Lower fan alarm
0
R
43
044
43
Middle fan alarm
0
R
44
045
44
High temperature alarm
0
R
45
046
45
Low temperature alarm
0
R
46
047
46
High humidity alarm
0
R
47
048
47
Low humidity alarm
0
R
48
049
48
High water temperature CW1
0
R
49
050
49
Low water temperature CW1
0
R
50
051
50
General Inverter Alarm
0
R
51
052
51
Discharge temperature alarm
0
R/W
52
053
52
Loss of power
0
R
53
054
53
Low pressure difference alarm
0
R/W
54
055
54
Flow switch CW1 alarm
0
R
55
056
55
Out of envelope alarm
0
R/W
56
057
56
Compressor fails to start alarm
0
R/W
57
058
57
Alarm state that shut off compressor
0
R
58
059
58
LowSH (low super heat) alarm -Valve A
0
R
59
060
59
EEV motor error -Valve A
0
R
60
061
60
Return temperature sensor fail
0
R
61
062
61
Return humidity sensor fail
0
R
BMS Parameters, Version 1.3 (cont.)