STULZ CyberRow Chilled Water Series Installation, Operation & Maintenance Manual
(
Dec.
, 2013)
4.5.4 Control Menu Loop
From the Control Menu you may select from 4 screen menus: Set points,
Alarm Set points, Clock and Version. The controller may be programmed by
the user to require level 1 password authorization to enter this menu loop
(see Section 4.2.6). Once password access is granted, you may select and
adjust the set points controlling the performance of the unit, enable alarms
and determine their set points and set the clock.
Press ( ) Key
Press ( ) Key
Press ( ) or ( ) Key
Press ( ) or ( ) Key
Press ( ) or ( ) Key
MAIN MENU
Alarm Log
CONTROL
Service
CONTROL
Version
SET
Alarm Set
CONTROL
Set
ALARM SET
Clock
CONTROL
Alarm Set
CLOCK
Version
CONTROL
Clock
VERSION
Set
The Set points (
SET
) screens allow you to view and adjust the
temperature and humidity setpoint control parameters and
compare them to system level operating data derived from the
various Sensor/Transmitter inputs. See Section 4.5.4.1.
The Alarm Set points
(
ALARM SET
)
screens allow you to enable
and adjust the high and low temperature and humidity alarm set
points and offsets and compare them to the control set points
and to the system level operating data derived from the Sensor/
Transmitter inputs. See Section 4.5.4.2.
Two Version screens are provided for information only. They show controller
hardware and software details that are useful to STULZ Product Support if
technical assistance is needed.
From the Clock screens you may view and adjust the current time,
date and day. See Section 4.5.4.3.
Information
Carel S.p.A.
Code:
Ver.:1.3
10/14/13
Manual code:
Bios: 5.18
28/11/11
Boot: 4.03
03/07/06
Information
pCO type: pCO3 Large
Total Flash:
2048KB
Ram:
512KB
Built-In type:
None
Main cycle:
3.4 cycles/s
285ms
Press (
)
Key
Press (
)
Key
4-20
Press
( )
Key
Control
Menu