STULZ CyberRow Chilled Water Series Installation, Operation & Maintenance Manual
(
Dec.
, 2013)
4-22
Temperature Alarm
Low alarm Enable:
Yes
Set Point
60.0°F
STATUS________________
Temp: 72.6°F Set:72.0°F
Dew: 50.1°F
Low Temperature Alarm
Humidity Alarm
High alarm Enable:
Yes
Set Point
70.0%
STATUS________________
Hum: 45.6% Set:45.0%
Dew: 50.1°F
High Humidity Alarm
Humidity Alarm
Low alarm Enable:
Yes
Set Point
30.%
STATUS________________
Hum: 45.6% Set:45.0%
Dew: 50.1°F
Low Humidity Alarm
The following 2 screens appear only if your unit is
factory confi gured to utilize an optional entering water
temperature (EWT) sensor input.
Water Temp Alarm
High alarm Enable:
Yes
Set Point
60.0°F
STATUS________________
EWT:
00.0°F
High Entering Water Temperature Alarm
Water Temp Alarm
Low alarm Enable:
Yes
Set Point
40.0°F
STATUS________________
EWT:
00.0°F
Low Entering Water Temperature Alarm
Following the alarm enable screens are the alarm offset
screens. From these screens you may adjust offsets for the
high and low alarm set points at which the alarm will be
cancelled. The entered offset applies to both the upper
and lower values entered in the Alarm Set points Screens.
The offset is subtracted when it's applied to the high alarm
setpoint and it is added when it's applied to the low alarm
setpoint.
EXAMPLE 1: Temperature Alarm Offset
Temperature Alarm
Offset:
5.0°F
STATUS________________
Temp: 72.6°F Set:72.0°F
Dew: 50.1°F
If the offset for the temperature alarm is set at 5.0°F
(default), the high temperature alarm will cancel when the
actual temperature drops to the High Temperature Alarm
setpoint (80.0°F) - the Offset (5.0°F)
or,
80.0°F - 5.0°F = 75.0°F
The High Temperature Alarm will cancel at 75°F.
Conversely, the low temperature alarm will cancel when
the actual temperature rises to the Low Temperature Alarm
setpoint (60.0°F) + the Offset (5.0°F)
or,
60.0°F + 5.0°F = 65.0°F
The Low Temperature Alarm will clear at 65.0°F
EXAMPLE 2: Humidity Alarm Offset
Humidity Alarm
Offset:
5.0%
STATUS________________
Temp: 72.6°F Set:72.0°F
Dew: 50.1°F
High Temperature Alarm Offset
If the offset for the humidity alarm is set at 5% (default),
the high humidity alarm will cancel when the actual
humidity drops to the High Humidity Alarm setpoint
(70.0%) - the Offset (5.0%)
or,
70.0% - 5.0% = 65.0%
The High Humidity Alarm will cancel at 65%.