STULZ CyberRow Chilled Water Series Installation, Operation & Maintenance Manual
(
Dec.
, 2013)
4-10
4.4 Controller
Operation
The
E²
Series controller is designed to control an air conditioning system in a space or process application to temperature
and humidity levels as defi ned by the user. Conditioned air is supplied to the space as needed to maintain the
temperature/humidity control set points.
The controller I/O module includes inputs and outputs as depicted in Figure 12. Not all the inputs and outputs shown below are
utilized, therefore, only the inputs/outputs needed for the specifi c A/C system type and application are enabled.
Figure 12- Control Inputs and Outputs
Digital
Inputs
Analog Out-
puts
Supply
Voltage
A
D
A
A
A
A
A
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
DX1 Liquid Line Solenoid
DX1 Compressor Enable
Fan(s) Enable
Humidifi er Enable
Custom Alarm 1
Summary Alarm
A
Variable Fan Speed- Lower
A
A
Variable Fan Speed- Middle
A
Variable Fan Speed- Upper
A
CW Valve 1
Serial
Communications
Remote Shutdown
Customer Alarm 1
Air Proving Switch
Fire/Smoke Detector
Moisture Alarm Detection
(Leak, Condensate Pan, Humidifi er Fail)
DX1 Low Pressure
DX1 High Pressure
Humid Lockout
Dual Power A
Dual Power B
Upper Supply Air Temperature
Lower Supply Air Humidity
Return Air Temperature
Middle Supply Air Temperature
Return Air Humidity
Static Pressure
Expansion I/O
Module(s)
Additional
E²
Controller(s)
E2
Controller
I/O Module
Digital
Outputs
Analog
Inputs