STULZ CyberRow Chilled Water Series Installation, Operation & Maintenance Manual
(
Dec.
, 2013)
4-52
Bit
Sensor Failures 1
Sensor Failures 2
3
Return temperature
Reserved
4
Return humidity
Reserved
5
Static air pressure
Reserved
6
Suction pressure
Reserved
7
Suction temperature
Reserved
8
Discharge pressure
Reserved
9
Reserved
Reserved
10
Remote temperature
Reserved
11
Remote humidity
Reserved
12
Entering water temperature
Reserved
13
Leaving water temperature
Reserved
14
Reserved
Reserved
15
Reserved
Reserved
4.9.6 Digital Input Packed Bit Variables
Bit
Digital Inputs 1
Digital Inputs 2
0
Remote shutdown
Customer alarm 2
1
Customer alarm 1
Customer alarm 3
2
Water
Reserved
3
Condensate pan
Reserved
4
Humidifi er
Reserved
5
Moisture
Reserved
6
Middle fan alarm
Reserved
7
Upper fan alarm
Reserved
8
Fire/smoke
Reserved
9
Lower fan alarm
Reserved
10
Dual power input A
Reserved
11
Dual power input B
Reserved
12
Circuit 1 low pressure
Reserved
13
Circuit 1 high pressure
Reserved
14
Pump alarm
Reserved
15
Humidifi er lockout
Reserved
4.9.7 Digital Output Packed Bit Variables
Bit
Digital Outputs 1
Digital Outputs 2
0
Global alarm
Reserved
1
Custom alarm 1
Reserved
2
Master fan enable
Reserved
3
DX1 enable
Reserved
4
DX1 liquid line solenoid
Reserved
5
Humidifi er enable
Reserved
6
Dual power output A
Reserved
7
Dual power output B
Reserved
BMS Parameters, Version 1.3 (cont.)