1.3 Power Configurations
The ac power distribution within the SH043-series cabinet can be configured in
one of the following three ways to provide the desired level of power redundancy
to the cabinet’s shelf-mounted peripheral devices:
•
Single cabinet power configuration
•
Dual shelf power configuration
•
Dual cabinet power configuration
A description of each configuration option follows.
1.3.1 Single Cabinet Power Configuration
In the single cabinet power configuration, shown in Figure 1–4, a single ac power
source and CDU (A) are used to supply ac power to a single
ac power supply
(A) in each shelf. This is the normal configuration for the cabinet, and it provides
no power redundancy to shelf peripheral devices.
Figure 1–4 Single Cabinet Power Configuration
AC POWER
SUPPLY A
CXO-3937A-MC
PRIMARY
AC POWER
(BLACK
CABLE)
SBB SHELF
PRIMARY
AC POWER
SOURCE
CDU A
Introduction 1–7