Table 1–1 SH043-Series Cabinet Specifications
Characteristic
Specification
Dimensions (nominal)
110.00 cm (43.31 in) height, 60.00 cm (23.62
in) width, 87.25 cm (34.35 in) depth
Weight
Empty cabinet (only 1 CDU installed)
Empty cabinet with shipping
packaging
Maximum configuration (2 BA350–
MA shelves, 8 SHDZZ–ZZ shelves
with 6 SHZBZ-ZZ disk drives in each,
2 CDUs)
140 kg (309 lb)
160 kg (353 lb)
290 kg (639 lb)
Agency compliance
FCC, UL, CSA, TÜV, and CE-mark
Electrical rating
SW5xx–AC
100–120 volts, 60 Hz, single phase, 20
amperes
SW5xx–AD
100–120/200–240 volts, 50/60 Hz, single
phase, 20/16 amperes
Temperature
+10°C to +35°C (+50°F to +95°F)
Reduce rating by 1.8°C for each 1000 m
altitude (1.0°F for each 1000 ft altitude)
Humidity
10 to 85 percent at maximum wet bulb
temperature of +32°C (+90°F) and minimum
dew point of +2°C (+36°F)
Recommended Environmental Limits†
Operating environment
Temperature
18°C to 24°C (64.4°F to 75.2°F) with an
average rate of change of 3°C/hour maximum
and a step change of 3°C or less
Relative humidity
40 to 60 percent (noncondensing) with a step
change of 10 percent or less (noncondensing)
Altitude
Up to 2400 m (8000 ft)
Air quality
(maximum particle count)
Not to exceed 500,000 particles per cubic foot
of air at a size of 0.5 micron or larger
Nonoperating environment
Temperature
–40°C to +66°C (–40°F to +151°F)
Relative humidity
10 to 80 percent noncondensing
Altitude
4900 m (16,000 ft)
†These limits are for optimum equipment performance and reliability.
Introduction 1–3