SSI700 User Manual Description of Function Codes
www.ssinverter.info
Value
Function
Description
26
Frequency 1 reached
Refer to the descriptions of P8-30 and P8-31.
27
Frequency 2 reached
Refer to the descriptions of P8-32 and P8-33.
28
Current 1 reached
Refer to the descriptions of P8-38 and P8-39.
29
Current 2 reached
Refer to the descriptions of P8-40 and P8-41.
30
Timing reached
If the timing function (P8-42) is valid, the terminal becomes
ON after the current running time of the AC drive reaches
the set time.
31
AI1 input limit exceeded
If AI1 input is larger than the value of P8-46 (AI1 input
voltage upper limit) or lower than the value of P8-45 (AI1
input voltage lower limit), the terminal becomes ON.
32
Load becoming 0
If the load becomes 0, the terminal becomes ON.
33
Reverse running
If the AC drive is in the reverse running state, the terminal
becomes ON.
34
Zero current state
Refer to the descriptions of P8-28 and P8-29.
35
Module temperature reached
If the heatsink temperature of the inverter module (P7-07)
reaches the set module temperature threshold (P8-47), the
terminal becomes ON.
36
Software current limit
exceeded Refer to the descriptions of P8-36 and P8-37.
37
Frequency lower limit reached
(having output at stop)
If the running frequency reaches the lower limit, the terminal
becomes ON. In the stop state, the signal is still ON.
38
Alarm output
If a fault occurs on the AC drive and the AC drive continues
to run, the terminal outputs the alarm signal.
39
Motor overheat warning
If the motor temperature reaches the temperature set in
P9-58 (Motor overheat warning threshold), the terminal
becomes ON.
You can view the motor temperature by using .
40
Current running time reached
If the current running time of AC drive exceeds the value of
P8-53, the terminal becomes ON.
Default
Parameter
Name
Function
Code
Group P5: Output Terminals
0: Running frequency
FMP function selection
P5-06
AO1 function selection
P5-07
The output pulse frequency of the FMP terminal ranges from 0.01 kHz to "Maximum FMP
output frequency" (P5-09). The value of P5-09 is between 0.01 kHz and 100.00 kHz.
The output range of AO1. The relationship between pulse and analog output ranges and
corresponding functions is listed in the following table.
Table 6-6 Relationship between pulse and analog output ranges
and corresponding functions
Value
Function
Range (Corresponding to Pulse or Analog Output Range
0.0%–100.0%)
0
Running frequency
0 to maximum output frequency
1
Set frequency
0 to maximum output frequency
2
Output current
0 to 2 times of rated motor current
3
Output torque (absolute value)
0 to 2 times of rated motor torque
4
Output power
0 to 2 times of rated power
5
Output voltage
0 to 1.2 times of rated AC drive voltage
6
Pulse input
0.01–100.00 kHz
7
AI1 0–10
V
8
AI2
0–10 V (or 0–20 mA)
9
Reserved
10
Length
0 to maximum set length
11
Count value
0 to maximum count value
12
Communication setting
0.0%–100.0%
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...