SSI700 User Manual Description of Function Codes
www.ssinverter.info
Default
Setting
Range
Parameter
Name
Function
Code
100.0%
0.0%–300.0% (rated motor current)
Any current reaching 1
P8-38
0.0%
0.0%–300.0% (rated motor current)
Any current reaching 1 amplitude
P8-39
100.0%
0.0%–300.0% (rated motor current)
Any current reaching 2
P8-40
0.0%
0.0%–300.0% (rated motor current)
Any current reaching 2 amplitude
P8-41
If the output current of the AC drive is within the positive and negative amplitudes of any
current reaching detection value, the corresponding DO becomes ON.
The SSI700 provides two groups of any current reaching detection parameters, including
current detection value and detection amplitudes, as shown in the following figure.
Figure 6-24 Any current reaching detection
Property
Default
Setting
Range
Parameter
Name
Function
Code
☆
0
0: Disabled
1: Enabled
Timing function
P8-42
☆
0
0: P8-44
1: AI1
2: AI2
3: Resered(100%of analog input
corresponds to the value of P8-44)
Timing duration
source
P8-43
☆
0.0 min
0.0–6500.0 min
Timing duration
P8-44
These parameters are used to implement the AC drive timing function.
If P8-42 is set to 1, the AC drive starts to time at startup. When the set timing duration is
reached, the AC drive stops automatically and meanwhile the corresponding DO becomes
ON.
The AC drive starts timing from 0 each time it starts up and the remaining timing duration
can be queried by D0-20.
The timing duration is set in P8-43 and P8-44, in unit of minute.
Property
Default
Setting
Range
Parameter
Name
Function
Code
☆
3.10V
0.00 V to P8-46
AI1 input voltage lower limit
P8-45
☆
6.80 V
P8-45 to 10.00 V
AI1 input voltage upper limit
P8-46
These two parameters are used to set the limits of the input voltage to provide protection
on the AC drive. When the AI1 input is larger than the value of P8-46 or smaller than the
value of P8-45, the corresponding DO becomes ON, indicating that AI1 input exceeds the
limit.
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...