SSI700 User Manual Function Code
www.ssinverter.info
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
5.0%
0.0%–100.0% (BRAKE control
hysteresis 1)
Frequency detection
hysteresis (BRAKE
control hysteresis 1)
P8-20
☆
0.0%
0.00–100% (maximum
frequency)
Detection range of
frequency reached
P8-21
☆
0
0: Disabled
1: Enabled
Jump frequency during
acceleration/deceleration
P8-22
-
-
-
reserved
P8-23
-
-
-
reserved
P8-24
☆
50.00
Hz
0.00 Hz to maximum frequency
Frequency detection
value (BRAKE control 2)
P8-28
☆
5.0%
0.0%–100.0% (BRAKE control
hysteresis 2)
Frequency detection
hysteresis (BRAKE
control hysteresis 2)
P8-29
☆
50.00
Hz
0.00 Hz to maximum frequency
Any frequency reaching
detection value 1
P8-30
☆
0.0%
0.0%–100.0% (maximum
frequency)
Any frequency reaching
detection amplitude 1
P8-31
☆
50.00
Hz
0.00 Hz to maximum frequency
Any frequency reaching
detection value 2
P8-32
☆
0.0%
0.0%–100.0% (maximum
frequency)
Any frequency reaching
detection amplitude 2
P8-33
☆
5.0%
0.0%–300.0% (rated motor
current)
Zero current detection
level
P8-34
☆
0.10s
0.00–600.00s
Zero current detection
delay time
P8-35
☆
200.0
%
0.0% (no detection)
0.1%–300.0% (rated motor
current)
Output overcurrent
threshold
P8-36
☆
0.00s
0.00–600.00s
Output overcurrent
detectiondelay time
P8-37
☆
100.0
%
0.0%–300.0% (rated motor
current)
Any current reaching 1
P8-38
☆
0.0%
0.0%–300.0% (rated motor
current)
Any current reaching 1
amplitude
P8-39
☆
100.0
%
0.0%–300.0% (rated motor
current)
Any current reaching 2
P8-40
☆
0.0%
0.0%–300.0% (rated motor
current)
Any current reaching 2
amplitude
P8-41
☆
0
0: Disabled
1: Enabled
Timing function
P8-42
☆
0
0: P8-44
1: AI1
2: AI2
3: Reserved (100%of analog
input corresponds to the value of
P8-44)
Timing duration source
P8-43
☆
0.0 min
0.0–6500.0 min
Timing duration
P8-44
☆
3.10V
0.00 V to P8-46
AI1 input voltage lower
limit
P8-45
☆
6.80 V
P8-45 to 10.00 V
AI1 input voltage upper
limit
P8-46
☆
75°C
0–100°C
Module temperature
threshold
P8-47
☆
0
0: Fan working during running
1: Fan working continuously
Cooling fan control
P8-48
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...