SSI700 User Manual Maintenance and Troubleshooting
www.ssinverter.info
Chapter 9 Maintenance and Troubleshooting
9.1 Routine Repair and Maintenance of the SSI700
9.1.1 Routine Maintenance
The influence of the ambient temperature, humidity, dust and vibration will cause the
aging of the devices in the AC drive, which may cause potential faults or reduce the
service life of the AC drive. Therefore, it is necessary to carry out routine and periodic
maintenance.
Routine maintenance involves checking:
•
Whether the motor sounds abnormally during running
•
Whether the motor vibrates excessively during running
•
Whether the installation environment of the AC drive changes.
•
Whether the AC drive's cooling fan works normally
•
Whether the AC drive overheats
Routine cleaning involves:
•
Keep the AC drive clean all the time.
•
Remove the dust, especially metal powder on the surface of the AC drive, to
prevent the dust from entering the AC drive.
•
Clear the oil stain on the cooling fan of the AC drive.
9.1.2 Periodic Inspection
Perform periodic inspection in places where inspection is difficult.
Periodic inspection involves:
Check and clean the air duct periodically.
Check whether the screws become loose.
Check whether the AC drive is corroded.
Check whether the wiring terminals show signs of arcing;
Main circuit insulation test
Before measuring the insulating resistance with megameter (500 VDC
megameter recommended), disconnect the main circuit from the AC drive.
Do not use the insulating resistance meter to test the insulation of the control
circuit. The high voltage test need not be performed again because it has
been completed before delivery.
Prompt
9.1.3 Replacement of Vulnerable Components
The vulnerable components of the AC drive are cooling fan and filter electrolytic capacitor.
Their service life is related to the operating environment and maintenance status.
Generally, the service life is shown as follows:
Judging Criteria
Possible Damage Reason
Service Life
Component
• Whether there is crack on the blade
• Whether there is abnormal vibration
noise upon startup
• Bearing worn
• Blade aging
2 to 3 years
Fan
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...