SSI700 User Manual EMC
www.ssinverter.info
Chapter 7 EMC
7.1 Definition of Terms
1) EMC
Electromagnetic compatibility (EMC) describes the ability of electronic and electrical
devices or systems to work properly in the electromagnetic environment and not to
generate electromagnetic interference that influences other local devices or systems.
In other words, EMC includes two aspects: The electromagnetic interference generated
by a device or system must be restricted within a certain limit; the device or system must
have sufficient immunity to the electromagnetic interference in the environment.
2) First environment
Environment that includes domestic premises, it also includes establishments directly
connected without intermediate transformers to a low-voltage power supply network which
supplies buildings used for domestic purposes
3) Second environment
Environment that includes all establishments other than those directly connected to a low-
voltage power supply network which supplies buildings used for domestic purposes
4) Category C1 AC drive
Power Drive System (PDS) of rated voltage less than 1000 V, intended for use in the first
environment
5) Category C2 AC drive
PDS of rated voltage less than 1000 V, which is neither a plug in device nor a movable
device and, when used in the first environment, is intended to be installed and
commissioned only by a professional
6) Category C3 AC drive
PDS of rated voltage less than 1000 V, intended for use in the second environment and
not intended for use in the first environment
7) Category C4 AC drive
PDS of rated voltage equal to or above 1000 V, or rated current equal to or above 400 A,
or intended for use in complex systems in the second environment
7.2 Introduction to EMC Standard
7.2.1 EMC Standard
The SSI700 series AC drive satisfies the requirements of standard EN 61800-3: 2004
Category C2. The AC drives are applied to both the first environment and the second
environment.
7.2.2 Installation Environment
The system manufacturer using the AC drive is responsible for compliance of the system
with the European EMC directive. Based on the application of the system, the integrator
must ensure that the system complies with standard EN 61800-3: 2004 Category C2, C3
or C4.
Warning
If applied in the first environment, the AC drive may generate radio interference. Besides the CE
compliance described in this chapter, users must take measures to avoid such interference, if
necessary.
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...