SSI700 User Manual Function Code
www.ssinverter.info
Chapter 5 Function Code Table
If 16-00 is set to a non-zero number, parameter protection is enabled. You must enter the
correct user password to enter the menu.
To cancel the password protection function, enter with password and set 16-00 to 0.
Group P are standard function parameters.
The symbols in the function code table are described as follows:
"
☆
": The parameter can be modified when the AC drive is in either stop or running state.
"
★
": The parameter cannot be modified when the AC drive is in the running state.
"
●
": The parameter is the actually measured value and cannot be modified.
"*": The parameter is factory parameter and can be set only by the manufacturer.
5 Standard Function Parameters
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P0: Standard Function Parameters
★
0
0:Sensorless flux vector control
(SFVC)
1: Voltage/Frequency (V/F)
control
Motor control mode
P0-00
☆
0
0:Operation panel control (LED off)
1: Terminal control (LED on)
2: Communication control (LED
blinking)
Command source
selection Run/Stop
P0-01
*
1
1:G type(constant torque load)
G/P(Motor) type display
P0-02
★
10
0: Digital setting Preset P0-08,
UP/DOWN Can be modified.
(non-retentive at power failure)
1: Digital setting Preset P0-08,
UP/DOWN Can be modified.
(retentive at power failure)
2: AI1
3: AI2
4: Reserved
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
10: Potentiometer key pad
Main frequency source
A selection
P0-03
★
1
The same as P0-03 (Main
frequency source A selection)
Auxiliary frequency
source B selection
P0-04
☆
0
0:Relative to maximum
frequency
1: Relative to main frequency A
Range of auxiliary
frequency B for A and B
operation
P0-05
☆
100%
0%–150%
Range of auxiliary
frequency B for A and B
operation
P0-06
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...