SSI700 User Manual Description of Function Codes
www.ssinverter.info
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
50.00
Hz
0.00 Hz to maximum frequency
Any frequency reaching
detection value 1
P8-30
☆
0.0%
0.0%–100.0% (maximum
frequency)
Any frequency reaching
detection amplitude 1
P8-31
☆
50.00
Hz
0.00 Hz to maximum frequency
Any frequency reaching
detection value 2
P8-32
☆
0.0%
0.0%–100.0% (maximum
frequency)
Any frequency reaching
detection amplitude 2
P8-33
If the output frequency of the AC drive is within the positive and negative amplitudes of
the any frequency reaching detection value, the corresponding DO becomes ON.
The SSI700 provides two groups of any frequency reaching detection parameters,
including frequency detection value and detection amplitude, as shown in the following
figure.
Figure 6-21 Any frequency reaching detection
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
5.0%
0.0%–300.0% (rated motor
current)
Zero current detection
level
P8-34
☆
0.10s
0.00–600.00s
Zero current detection
delay time
P8-35
If the output current of the AC drive is equal to or less than the zero current detection level
and the duration exceeds the zero current detection delay time, the corresponding DO
becomes ON. The zero current detection is shown in the following figure.
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...