SSI700 User Manual Description of Function Codes
www.ssinverter.info
Figure 6-31 Reaching the set count value and designated count value
Group 12: Multi-Reference and Simple PLC Function
The SSI700 multi-reference has many functions. Besides multi-speed, it can be used as
the setting source of the V/F separated voltage source and setting source of process PID.
In addition, the multi-reference is relative value.
The simple PLC function is different from the SSI700 user programmable function. Simple
PLC can only complete simple combination of multi-reference, while the user
programmable function is more practical.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group 12: Multi-Reference and Simple PLC Function
☆
0.0%
-100.0%~100.0%
Reference 0
12-00
☆
0.0%
-100.0%~100.0%
Reference 1
12-01
☆
0.0%
-100.0%~100.0%
Reference 2
12-02
☆
0.0%
-100.0%~100.0%
Reference 3
12-03
☆
0.0%
-100.0%~100.0%
Reference 4
12-04
☆
0.0%
-100.0%~100.0%
Reference 5
12-05
☆
0.0%
-100.0%~100.0%
Reference 6
12-06
☆
0.0%
-100.0%~100.0%
Reference 7
12-07
☆
0.0%
-100.0%~100.0%
Reference 8
12-08
☆
0.0%
-100.0%~100.0%
Reference 9
12-09
☆
0.0%
-100.0%~100.0%
Reference 10
12-10
☆
0.0%
-100.0%~100.0%
Reference 11
12-11
☆
0.0%
-100.0%~100.0%
Reference 12
12-12
☆
0.0%
-100.0%~100.0%
Reference 13
12-13
☆
0.0%
-100.0%~100.0%
Reference 14
12-14
☆
0.0%
-100.0%~100.0%
Reference 15
12-15
Multi-reference can be the setting source of frequency, V/F separated voltage and
process PID. The multi-reference is relative value and ranges from -100.0% to 100.0%.
As frequency source, it is a percentage relative to the maximum frequency. As V/F
separated voltage source, it is a percentage relative to the rated motor voltage. As
process PID setting source, it does not require conversion.
Multi-reference can be switched over based on different states of DI terminals. For details,
see the descriptions of group P4.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group 12: Multi-Reference and Simple PLC Function
☆
0
0: Stop after the AC drive runs one cycle
1: Keep final values after the AC drive
runs one cycle
2: Repeat after the AC drive runs one
cycle
Simple PLC
running mode
12-16
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...