SSI700 User Manual Description of Function Codes
www.ssinverter.info
Figure 6-20 Acceleration/deceleration time switchover
During acceleration, if the running frequency is smaller than the value of P8-25,
acceleration time 2 is selected. If the running frequency is larger than the value of P8-25,
acceleration time 1 is selected.
During deceleration, if the running frequency is larger than the value of P8-26,
deceleration time1 is selected. If the running frequency is smaller than the value of P8-26,
deceleration time 2 is selected.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
0
0: Disabled
1: Enabled
Terminal JOG preferred
P8-27
It is used to set whether terminal JOG is preferred.
If terminal JOG is preferred, the AC drive switches to terminal JOG running state when
there is a terminal JOG command during the running process of the AC drive.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
50.00
Hz
0.00 Hz to maximum frequency
Frequency detection
value (BRAKE control 2)
P8-28
☆
5.0%
0.0%–100.0% (BRAKE control
hysteresis 2)
Frequency detection
hysteresis (BRAKE
control hysteresis 2)
P8-29
The frequency detection function is the same as BRAKE control 1 function. For details,
refer to the descriptions of P8-19 and P8-20.
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...