SSI700 User Manual Description of Function Codes
www.ssinverter.info
Figure 6-17 BRAKE control level
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P8: Auxiliary Functions
☆
0.0%
0.00–100% (maximum
frequency)
Detection range of
frequency reached
P8-21
If the AC drive running frequency is within the certain range of the set frequency, the
corresponding DO terminal becomes ON.
This parameter is used to set the range within which the output frequency is detected to
reach the set frequency. The value of this parameter is a percentage relative to the
maximum frequency. The detection range of frequency reached is shown in the following
figure.
Figure 6-18 Detection range of frequency reached