SSI700 User Manual Description of Function Codes
www.ssinverter.info
•
0: Two-line mode 1
It is the most commonly used two-line mode, in which the forward/reverse rotation of the
motor is decided by DI1 and DI2. The parameters are set as below:
Function Description
Value
Parameter
Name
Function
Code
Two-line 1
0
Terminal command mode
P4-11
Forward RUN (FWD)
1
DI1 function selection
P4-00
Reverse RUN (REV)
2
DI2 function selection
P4-01
Figure 6-7 Setting of two-line mode 1
K1
K2
RUN
command
1 0
Forward
RUN
0 1
Reverse
RUN
1 1
Stop
0 0
Stop
As shown in the preceding figure, when only K1 is ON, the AC drive instructs forward
rotation. When only K2 is ON, the AC drive instructs reverse rotation. When K1 and K2
are ON or OFF simultaneously, the AC drive stops.
•
1: Two-line mode 2
In this mode, DI1 is RUN enabled terminal, and DI2 determines the running direction. The
parameters are set as below:
Function Description
Value
Parameter
Name
Function
Code
Two-line 1
1
Terminal command mode
P4-11
Forward RUN (FWD)
1
DI1 function selection
P4-00
Reverse RUN (REV)
2
DI2 function selection
P4-01
Figure 6-8 Setting of two-line mode 2
K1
K2
RUN
command
1 0
Forward
RUN
1 1
Reverse
RUN
0 0
Stop
0 1
Stop
As shown in the preceding figure, if K1 is ON, the AC drive instructs forward rotation when
K2 is OFF, and instructs reverse rotation when K2 is ON. If K1 is OFF, the AC drive stops.
•
2: Three-line mode 1
In this mode, DI3 is RUN enabled terminal, and the direction is decided by DI1 and DI2.
The parameters are set as below:
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...