
SSI700 User Manual Description of Function Codes
www.ssinverter.info
If the value of a certain digit is 1, when analog input voltage is less than the minimum
input, the corresponding value of this analog input is 0.0%.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P4: Input Terminals
★
0.0s
0.0–3600.0s
DI1 delay time
P4-35
★
0.0s
0.0–3600.0s
DI2 delay time
P4-36
These parameters are used to set the delay time of the AC drive when the status of DI
terminals changes.
Currently, only DI1, DI2 support the delay time function.
Property
Default
Setting
Range
Parameter
Name
Function
Code
★
00000
Unit's digit (DI1 valid mode)
DI valid mode
selection1
P4-38
0: High level valid
1: Low level valid
Ten's digit (DI2 valid mode)
0, 1 (same as DI1)
Hundred's digit (DI3 valid mode)
0, 1 (same as DI1)
Thousand's digit(DI4 valid mode)
0, 1 (same as DI1)
Ten thousand's digit(DI5 valid mode)
0, 1 (same as DI1)
These parameters are used to set the valid mode of DI terminals.
•
0: High level valid
The DI terminal is valid when being connected with COM, and invalid when being
disconnected from COM.
•
1: Low level valid
The DI terminal is invalid when being connected with COM, and invalid when being
disconnected from COM.
Group F5: Output Terminals
The SSI700 provides an analog output (AO) terminal, a digital output (DO) terminal, a
relay terminal and a FM terminal (used for high-speed pulse output or open-collector
switch signal output) as standard.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group P5: Output Terminals
☆
0
0: Pulse output (FMP)
1: Switch signal output (FMR)
FM terminal output mode
P5-00
The FM terminal is programmable multiplexing terminal. It can be used for high-speed
pulse output (FMP), with maximum frequency of 100Hz. Refer to P5-06 for relevant
functions of FMP. It can also be used as open collector switch signal output (FMR).
Default
Parameter
Name
Function Code
0
FMR function (opencollector output terminal)
P5-01
2
Relay function (T/A-T/B-T/C)
P5-02
4
DO1 function selection (open-collector output terminal)
P5-04
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...